Siemens Fault 0a7991 New! Link

Fault Report: Siemens Fault 0A7991

Disable the Identification ManuallyIf you do not wish to run the identification (e.g., during bench testing or Factory Acceptance Tests (FAT)), change these parameters: siemens fault 0a7991

If you do not wish to perform the identification (e.g., during bench testing without a motor), you can disable it via the Siemens Parameter List: In TIA Portal, add Organization Block OB 122

If the alarm does not disappear or prevents the drive from running, use the following methods to resolve it: 1. Complete the Identification Routine If you do not wish to perform the identification (e

9. Collect info before contacting support

Prepare:

Manual Override (Disable):If you cannot run the identification (e.g., during a Factory Acceptance Test without a motor), you can force the alarm to clear by manually changing settings: Set p1900 = 0 (Inhibits Motor ID). Set p1300 = 0 (Switches to V/f standard control mode).